Sockets in UK Bathrooms: What the Rules Allow

Can you have a plug socket in a UK bathroom? The 2.5 metre rule, shaver sockets, zones, RCD protection and who can legally fit them in Wales.

Sockets in UK Bathrooms: What the Rules Allow

Bathroom socket positioned far from the bath

You can have a standard three-pin socket in a UK bathroom only if it sits at least 2.5 metres horizontally from the edge of the bath or shower tray, which in most family bathrooms means you can’t. The usual answer is a shaver supply unit, the one outlet type the rules allow close to the water. Whatever you choose, the work must be done by a registered electrician and signed off. The best moment to settle all of this is before the room is stripped, when the layout is still on paper, and that is how we approach every bathroom renovation in Cardiff and the Vale of Glamorgan.

Jmplumbingservicesltd
Plan Bathroom Power Before Renovation
JM Plumbing Services Ltd renovates bathrooms across Cardiff and the Vale of Glamorgan, helping you plan your room around your needs.
Visit

TL;DR

  • A normal 13A socket must be at least 2.5 metres from the edge of a bath or shower tray. Most bathrooms are too small to meet that.
  • A shaver supply unit (the “shavers only” outlet) is the permitted alternative near the bath. It is meant for shavers and electric toothbrushes, not hairdryers.
  • Every circuit serving a bathroom needs 30 mA RCD protection, including lights, extractor fans and heated towel rails.
  • In Wales, bathroom electrical work is notifiable, so use an installer registered with a competent person scheme and expect a certificate.
  • Decide where power goes at the design stage, before tiles and plumbing are fixed.

Table of Contents

The short answer: can you have a plug socket in a bathroom?

The 2.5 metre figure comes from the UK wiring standard, BS 7671, which electricians work to. Its bathroom section (Section 701) says standard 13A, 230V socket-outlets are prohibited within 2.5 metres horizontally of zone 1, the area directly around the bath or shower. The only exceptions are SELV sockets (very low voltage, safe by design) and shaver supply units.

You may still read “3 metres” online. That was the distance in the 17th Edition of the wiring regulations from 2008. The current rule is 2.5 metres measured from the zone 1 boundary.

This is not fussiness. Electrical Safety First points out that wet skin lowers the body’s resistance, which makes the bathroom one of the highest-risk rooms in a home for electric shock.

A worked example

Take a 2.4 metre by 1.9 metre family bathroom with a bath along the short wall. Zone 1 starts at the edge of the bath. Even the furthest corner of the room is under 2.5 metres from it, so there is nowhere a standard socket can legally go. A large en-suite or a big room with a separate shower corner may have a wall far enough away, but you have to measure from the zone boundary, not from the shower door.

Worked example showing bathroom socket exclusion distance

Understanding bathroom zones in plain English

The rules divide the room into zones around the bath or shower, and each zone has its own limits on what electrical equipment may be fitted. Here is how the Select pocket guide to Section 701 sets them out:

Zone Where it is What may be fitted
0 Inside the bath or shower tray Only fixed equipment rated IPX7 and on very low voltage (SELV, up to 12 V AC)
1 Directly above the bath or shower, up to 2.25 m high Fixed equipment rated at least IPX4, such as electric showers, towel rails and suitable lights
2 A further 0.6 m beyond zone 1, same height IPX4 equipment, SELV switches and sockets, and shaver supply units
Outside the zones Rest of the room Standard sockets only if at least 2.5 m from the zone 1 boundary

The figures come from the Select guide to bathroom installations. An IP rating (for example IPX4) tells you how well a fitting resists water: IPX4 means it withstands splashing from any direction.

For a shower with no tray or basin, zone 1 extends 1.2 metres horizontally from the centre of the fixed water outlet. This matters if you are planning a wet room, where the whole floor area is effectively wet and the zones need careful mapping before any wiring is done.

If you want to read more about how ratings and zones work together, our blog has articles on bathroom electrical zones and on IP ratings for bathroom zones.

Why shaver sockets exist

The outlet marked “shavers only” is not a loophole. A shaver supply unit built to BS EN 61558-2-5 contains an isolating transformer, so the output is electrically separated from the mains. Electrical Safety First confirms that shaver points are allowed within 2.5 metres provided they are SELV or conform to that standard, and the Select guide places them in zone 2 where direct shower spray is unlikely.

In practice:

  • They are low power, so they suit electric shavers and toothbrushes, not hairdryers, straighteners or heaters.
  • Many have a dual voltage output, though you should follow the maker’s rating on the unit.
  • They are normally fitted at a comfortable height beside the mirror, away from the shower itself.

If you want to dry your hair at the mirror, the legal answer is to do it in a bedroom or another room with a compliant socket, or to site a socket outside the bathroom on the other side of the door.

What about extension leads and plug-in gadgets?

Never run an extension lead from a landing or hallway socket into the bathroom. Electrical Safety First advises that where a bathroom has no sockets, extension leads should not be used to power appliances because it raises the risk of electric shock. The same applies to charging phones or tablets on a lead while in the bath.

If your bathroom wiring does not have RCD protection, the same page recommends using an RCD plug on the socket where the product is plugged in. An RCD (residual current device) cuts the power in a fraction of a second if it senses current leaking, for example through a person.

RCD protection: the rule that covers every circuit

Since the 17th Edition in 2008, all circuits in a bathroom need RCD protection, not just the shower. That means lighting, extractor fans, electric showers and heated towel rails. Regulation 701.411.3.3 asks for a rated residual current of no more than 30 mA on low voltage circuits serving the location and on circuits that pass through zones 1 or 2.

Older homes are where this catches people. If your house was last rewired before RCD consumer units became common, a bathroom refit is a good moment to have the board checked. Your electrician will tell you whether the circuits feeding the new room are protected.

Supplementary bonding, the extra earth links between metal pipes and fittings, can be left out only if three conditions are met: circuits meet disconnection requirements, all have 30 mA RCDs, and all metal parts are connected to the main protective bonding. Otherwise it must be installed for any addition or alteration to an existing bathroom. Your electrician decides which applies.

RCD protection: the rule that covers every circuit

Lights, extractors and towel rails: the power you do need

Most people asking about sockets are really asking where their power will come from. A modern bathroom normally needs:

  1. Lighting. Fittings in zone 1 must be at least IPX4, and many people choose sealed downlights across the ceiling. See our notes on lights in bathroom zones and bathroom lighting regulations.
  2. An extractor fan. It is usually wired through a fused spur or the lighting circuit, not a plug.
  3. A heated towel rail. Fixed electric rails are permitted in zone 1 if rated IPX4 or better, and hard-wired rather than plugged in.
  4. An electric shower. Electrical Safety First advises it should be fitted by a registered electrician on its own circuit.
  5. A shaver supply unit, if you want somewhere to plug in a shaver or toothbrush.

If you want a socket for a mirror with built-in lighting or a heated mirror, check the product’s instructions and discuss it with your electrician. Many of these are hard-wired or supplied with a low voltage driver placed outside the zones.

What changed recently

The wiring regulations are updated in amendments. Guidance published in 2026 notes that BS 7671:2018+A4:2026 was published on 15 April 2026, with the previous edition remaining valid during a transition until 15 October 2026, after which new work should follow Amendment 4. Your electrician will already be working to the right edition. For homeowners the practical point is the same: ask for the certificate at the end of the job, which confirms the work was designed, installed and tested to the standard in force.

Who can legally fit bathroom electrics in Wales

In Cardiff and the Vale of Glamorgan, the building regulations apply. Part P of the regulations covers fixed electrical installations in homes, and it has applied since 1 January 2005. Wales has its own rules, and English checklists should not be applied to a Welsh job.

GOV.WALES says to use an installer registered with a competent person scheme or seek Building Control approval. Bathroom socket work is not exempt from notification. The schemes for electrical work in homes include BESCA, Blue Flame Certification, Certsure, NAPIT, OFTEC and Stroma. A registered installer notifies the local authority and issues a certificate of compliance.

What to ask for:

  • The electrician’s scheme membership, which you can check on the Competent Persons Register.
  • A compliance certificate, which GOV.WALES says to expect within 30 days of completion.
  • A completed Electrical Installation Certificate for the work.

This is a step the law gives to a registered electrician and the local authority, so treat it as part of the project, not an optional extra. Keep the paperwork: it is what a buyer’s solicitor will ask for when you sell, and it is part of what protects your home’s value after a renovation. Our blog collects guidance on building regulations for bathrooms if you want the wider picture.

Planning sockets and power into a renovation

If you are replacing a bathroom, the sequence matters, because cables have to go in before walls are boarded and tiled.

  1. Measure your room against the zones. Mark the bath or shower edge, add 2.5 m, and see whether any wall space remains. For most rooms it will not.
  2. Decide your power list. Lights, fan, towel rail, shower and shaver unit. Place each one on the plan, noting its zone and IP rating.
  3. Choose the layout with the wiring in mind. Moving a shower or bath changes the zones, and so changes where fittings can go. It is far cheaper to decide this on paper than after the tiles are up.
  4. Fix wiring, then plumbing and waterproofing, then tiling. Cable routes for lights and fans have to be settled before boards and tile go on.
  5. Test, certify and notify. Your electrician tests the circuits, issues the certificate and notifies Building Control through their scheme.

A wet room adds another layer, because the entire floor is wet and the zones spread across much of the room. That is a reason to plan the electrics together with the drainage and waterproofing, not as an afterthought.

Where the money goes

Our bathroom renovation service in Cardiff is published from £2,500 to £4,000 as a one-off price. We state this as the published range for the renovation service itself. A shaver unit or extra lighting circuits are part of the overall scope you agree up front, which is why settling the power list at the planning stage avoids surprises later.

Why one team makes this easier

The awkward part of bathroom electrics is not the rule itself. It is that the answer depends on where the bath, shower, basin and door end up, and those decisions are made by different trades at different times. When layout, plumbing, tiling and flooring are planned by one accountable local team, the zones can be drawn onto the plan before anything is ordered, and a socket that cannot legally go where you imagined is found at the drawing stage, not at the inspection.

That is the idea behind how we work: one team, fixed pricing and no showroom markup, with every job given proper attention whatever its size. Our customers have left 25 verified 5-star Google reviews.

Our view

Most of the bathroom power questions we hear start the same way: “Why can’t I just put a socket next to the mirror?” The honest answer is that the rules are there because water and mains electricity are a bad mix, and the layout of a small UK bathroom rarely leaves room for a standard socket.

What we tell homeowners is to think about what they actually want to do in the room. Shave, brush teeth, light the room well, keep a towel rail warm, run a shower. Every one of those has a compliant answer, from a shaver unit to a properly rated light and a hard-wired rail. The thing that goes wrong is leaving it until the room is half built.

We prefer to design the bathroom as a whole, so the layout, plumbing, tiling and finish are agreed together and the electrical work is planned in at the start. It is how a renovation stays on schedule, and how you end up with a room that looks good and passes its paperwork.

James

Planning a bathroom in Cardiff or the Vale?

If you are renovating or converting, we install bathrooms, en-suites, cloakrooms and wet rooms across Cardiff and the Vale of Glamorgan, together with the tiling and LVT or vinyl flooring that finish them. See our bathroom fitters in Cardiff page, or the page for bathroom fitters in Barry if you are in the Vale. Tell us how you use the room and we will plan the layout around it.

Jmplumbingservicesltd

For wet rooms, en-suites and cloakrooms, start from our main services page.

FAQ

Can I have a plug in my bathroom?

Only a standard socket at least 2.5 metres from the edge of the bath or shower tray, which few bathrooms allow. Shaver supply units and SELV sockets are the permitted exceptions nearer the water. Any new socket must be fitted by a registered electrician.

Why do bathroom sockets say “shavers only”?

They contain an isolating transformer, so the output is separated from the mains and is low power. That is why they are allowed in zone 2 while an ordinary 13A socket is not. They suit shavers and electric toothbrushes, not hairdryers or heaters.

Do I need an RCD for a bathroom light or fan?

Yes. Since 2008 all circuits serving a bathroom need 30 mA RCD protection, not only the shower. This includes lights, extractor fans and heated towel rails. Your electrician will confirm what your consumer unit provides.

Do I need a certificate for new bathroom electrics in Wales?

Yes. Bathroom socket work is notifiable in Wales, so use an installer registered with a competent person scheme. They should notify the local authority and give you a compliance certificate, which GOV.WALES says to expect within 30 days.

Can I use an extension lead in the bathroom?

No. Electrical Safety First advises against extension leads for powering appliances in a bathroom, because they increase the risk of electric shock. Use a compliant shaver unit, or move the appliance to another room.